NEC 690.8 DC Conductor Ampacity & Temperature Derating Calculator
NEC 690.8 requires sizing conductors to the larger of: Method 1: 156.25% of Isc (no derating applied), or Method 2: 125% of maximum circuit current (Isc × 1.25) after applying ambient temperature correction and conduit fill adjustment factors to the conductor's ampacity. The conductor must have ampacity ≥ the required current in both methods, using the larger result.
Interactive Parameters & Live Verdict
Rule Diagnostics & Recommendations
Engineering Formula & Verification Notes
Calculations follow NEC 690.8(B). Method 1 (156% rule) ignores environmental factors. Method 2 requires the conductor to carry 100% of the maximum circuit current after applying temperature correction (Table 310.15(B)(2)(a)) and conduit fill adjustment (Table 310.15(B)(3)(a)).
Worked Engineering Example
For a 10A Isc module string, Method 1 requires 15.6A capacity. If ambient temps and conduit fill result in a 0.7 correction factor, a 40A wire (90°C) derates to 28A. Since 28A > 15.6A, the wire is compliant.
- Always use 90°C column for THWN-2/PV wire
- Method 1 is the '156% rule'
- Method 2 accounts for real-world heat and bundling
Common Sizing & Compatibility Mistakes
Engineers often forget that both methods must be checked independently.
- Using 75°C column instead of 90°C for PV wire
- Ignoring temperature additions for rooftop conduit
- Failing to count all current-carrying conductors in a bundle
Reference Benchmarks
| Wire Gauge | 90°C Ampacity | Typical Use |
|---|---|---|
| #12 AWG | 30 A | Small String |
| #10 AWG | 40 A | Home-run |
| #6 AWG | 75 A | Commercial DC |
Frequently Asked Technical Questions
Why 156%?
It is the product of two 125% factors: one for continuous load and one for high irradiance conditions.
Can I use 75°C ratings?
Yes, but it results in a lower ampacity, requiring larger wire gauges for the same current.
Does this include voltage drop?
No, voltage drop is a separate performance calculation (typically <3%).