Solar Array & LiFePO4 Battery Bank Sizing Simulator
To power a 5,000 Wh daily load with 2 days of autonomy using 48V LiFePO4 batteries (80% usable DoD and 90% inverter efficiency), you need a 13.9 kWh battery bank and roughly 1,620 W of solar panels assuming 4.5 peak sun hours.
Interactive Parameters & Live Verdict
Rule Diagnostics & Recommendations
Engineering Formula & Verification Notes
Battery sizing accounts for 90% DC-to-AC inverter efficiency, selected Depth of Discharge (DoD), and a 15% cold-weather capacity derate when sub-freezing operation is enabled. Solar PV sizing uses a 0.77 system derating factor (MPPT efficiency, wiring losses, panel temperature, and soiling).
Worked Example: 5 kWh Daily Cabin Load with 2-Day Winter Autonomy
A 5,000 Wh/day load over 2 days requires 10,000 Wh net AC energy. Dividing by 0.90 inverter efficiency and 0.80 LiFePO4 DoD gives 13,889 Wh (13.9 kWh) nameplate battery capacity—nearly three standard 48V 100Ah (5.12 kWh) server-rack modules.
- Size PV wattage against worst-month peak sun hours rather than summer averages if you rely on solar year-round.
- Account for inverter idle self-consumption (30–70W continuous = 0.7–1.7 kWh/day).
Common Off-Grid Sizing Mistakes
Underestimating inverter standby draw and winter irradiance causes premature low-voltage shutdowns.
- Charging standard unheated LiFePO4 cells below 0°C without low-temp BMS cutoff.
- Forgetting the 0.77 real-world PV derate factor for heat, MPPT, and wiring losses.
LiFePO4 vs. AGM Sizing Comparison (5 kWh/day, 2 Days)
| Chemistry | Usable DoD | Required Nameplate Bank | Cycle Life |
|---|---|---|---|
| LiFePO4 (LFP) | 80–90% | 13.9 kWh | 4,000–6,000 cycles |
| Lead-Acid / AGM | 50% | 22.2 kWh | 500–800 cycles |
| Heated LFP (Cold) | 80% | 16.0 kWh | 4,000+ cycles |
Frequently Asked Technical Questions
Why divide solar daily watt-hours by 0.77?
Real-world PV arrays lose ~23% to panel heat, inverter/MPPT conversion, and cable voltage drop compared to STC lab ratings.
Why use 51.2V instead of 48V for LiFePO4 Ah conversion?
A 16-cell LiFePO4 pack has a nominal voltage of 16 × 3.2V = 51.2V.
Can I mix different battery ages in one bank?
Avoid mixing old and new cells in series; parallel self-managed 51.2V server-rack packs with BMS balancing are safer.