Calculator
Confidence 85%
NEC 625.41 requires sizing circuits at 125% of EVSE continuous load. For a 48A charger, minimum circuit rating is 60A. Voltage drop must stay under 3% for branch circuits (NEC informational note). The correct voltage drop formula is Vd% = (2 × K × I × L) / (CM × V) × 100, where K=12.9 (Cu) or 21.2 (Al), I=current, L=one-way distance, CM=circular mils of wire gauge, V=system voltage. Wire selection requires checking both ampacity (NEC Table 310.16) and voltage drop. For 48A at 100ft on 240V: 6 AWG copper (26,240 cmil) gives ~1.95% drop, 8 AWG (16,510 cmil) gives ~3.1% drop. Aluminum requires 1-2 sizes larger than copper for same ampacity.