EV Charger Feeder Wire Size & Voltage Drop Calculator

Verified Nov 17, 2026 Quality 100/100 Confidence 85% 0 Evaluations
VERIFIED QUICK ANSWER

NEC 625.41 requires sizing circuits at 125% of EVSE continuous load. For a 48A charger, minimum circuit rating is 60A. Voltage drop must stay under 3% for branch circuits (NEC informational note). The correct voltage drop formula is Vd% = (2 × K × I × L) / (CM × V) × 100, where K=12.9 (Cu) or 21.2 (Al), I=current, L=one-way distance, CM=circular mils of wire gauge, V=system voltage. Wire selection requires checking both ampacity (NEC Table 310.16) and voltage drop. For 48A at 100ft on 240V: 6 AWG copper (26,240 cmil) gives ~1.95% drop, 8 AWG (16,510 cmil) gives ~3.1% drop. Aluminum requires 1-2 sizes larger than copper for same ampacity.

Interactive Parameters & Live Verdict

Rule Diagnostics & Recommendations

    Engineering Formula & Verification Notes

    Calculations use the circular mil method (Vd = 2*K*I*L / CM). K=12.9 for Copper, 21.2 for Aluminum. NEC 625.41 requires 125% continuous load sizing.

    Worked Engineering Example

    For a 48A charger at 100ft using copper wire:

    • Circuit rating: 48A * 1.25 = 60A breaker.
    • Voltage drop: (2 * 12.9 * 48 * 100) / (16510 * 240) = 3.1%.
    • Recommendation: Upsize to 4 AWG to stay under 3%.

    Common Sizing & Compatibility Mistakes

    Engineers often overlook the difference between ampacity and voltage drop.

    • Ignoring terminal temperature ratings (75°C).
    • Measuring straight-line distance instead of actual wire path.
    • Failing to account for total feeder + branch drop (5% limit).

    Reference Benchmarks

    Reference Benchmarks
    Charger Amps Min Breaker Recommended Copper AWG
    32A 40A 8 AWG
    40A 50A 6 AWG
    48A 60A 6 AWG

    Frequently Asked Technical Questions

    Why 125%?

    NEC 625 classifies EV charging as a continuous load, requiring 125% capacity to prevent overheating.

    Is 3% drop mandatory?

    It is an NEC informational note recommendation, but often required by local inspectors and equipment warranties.

    Does aluminum require larger wire?

    Yes, aluminum has higher resistance and typically requires one to two gauges larger than copper.