Off-Grid Solar DC Disconnect & Circuit Breaker Sizing Calculator

Verified Nov 22, 2026 Quality 100/100 Confidence 85% 0 Evaluations
VERIFIED QUICK ANSWER

Size DC breakers by applying a 1.25 factor to module Isc for continuous load, then dividing by 0.80 for OCPD rating. Ensure voltage rating exceeds 1.2 x Voc x Ns where Ns is modules in series. Verify Interrupting Capacity (kA) requirements for fault conditions.

Interactive Parameters & Live Verdict

Rule Diagnostics & Recommendations

    Engineering Formula & Verification Notes

    Calculations follow NEC 690 guidelines: 1.25 multiplier for continuous current and 1.20 multiplier for voltage temperature correction. Breaker sizing assumes 80% continuous duty rating.

    Worked Engineering Example

    For a system with 9A Isc, 2 parallel strings, 40V Voc, and 10 modules in series:

    • Max Circuit Current: 9 * 2 * 1.25 = 22.5A
    • Min Breaker Rating: 22.5 / 0.8 = 28.1A (Round up to 30A)
    • Min Voltage Rating: 40 * 10 * 1.2 = 480V

    Common Sizing & Compatibility Mistakes

    Engineers often overlook the non-zero-crossing nature of DC current.

    • Using AC-rated breakers in DC circuits, which fail to quench arcs.
    • Ignoring temperature correction factors for voltage.
    • Failing to verify the Interrupting Capacity (kA) for fault conditions.

    Reference Benchmarks

    Reference Benchmarks
    System Size Voltage Current
    Residential 600V 30-60A
    Storage-Ready 600V 100-250A
    Commercial 1000V 200-600A

    Frequently Asked Technical Questions

    Can I use an AC breaker for DC?

    No. DC current is continuous and harder to interrupt; using an AC breaker poses a severe fire risk.

    Why the 1.25 factor?

    NEC requires a 125% safety margin for continuous loads to prevent nuisance tripping.

    What is interrupt rating?

    It is the maximum fault current the device can safely clear without exploding or welding shut.