Off-Grid Solar DC Disconnect & Circuit Breaker Sizing Calculator
Size DC breakers by applying a 1.25 factor to module Isc for continuous load, then dividing by 0.80 for OCPD rating. Ensure voltage rating exceeds 1.2 x Voc x Ns where Ns is modules in series. Verify Interrupting Capacity (kA) requirements for fault conditions.
Interactive Parameters & Live Verdict
Rule Diagnostics & Recommendations
Engineering Formula & Verification Notes
Calculations follow NEC 690 guidelines: 1.25 multiplier for continuous current and 1.20 multiplier for voltage temperature correction. Breaker sizing assumes 80% continuous duty rating.
Worked Engineering Example
For a system with 9A Isc, 2 parallel strings, 40V Voc, and 10 modules in series:
- Max Circuit Current: 9 * 2 * 1.25 = 22.5A
- Min Breaker Rating: 22.5 / 0.8 = 28.1A (Round up to 30A)
- Min Voltage Rating: 40 * 10 * 1.2 = 480V
Common Sizing & Compatibility Mistakes
Engineers often overlook the non-zero-crossing nature of DC current.
- Using AC-rated breakers in DC circuits, which fail to quench arcs.
- Ignoring temperature correction factors for voltage.
- Failing to verify the Interrupting Capacity (kA) for fault conditions.
Reference Benchmarks
| System Size | Voltage | Current |
|---|---|---|
| Residential | 600V | 30-60A |
| Storage-Ready | 600V | 100-250A |
| Commercial | 1000V | 200-600A |
Frequently Asked Technical Questions
Can I use an AC breaker for DC?
No. DC current is continuous and harder to interrupt; using an AC breaker poses a severe fire risk.
Why the 1.25 factor?
NEC requires a 125% safety margin for continuous loads to prevent nuisance tripping.
What is interrupt rating?
It is the maximum fault current the device can safely clear without exploding or welding shut.