Victron Cerbo GX Relay Auto Start Generator Fuel Level Calibration Calculator

Verified Nov 17, 2026 Quality 100/100 Confidence 100% 0 Evaluations
VERIFIED QUICK ANSWER

Calculate optimal Victron Cerbo GX Relay 1 auto-start and stop thresholds based on battery State of Charge (SOC). Ensure safe dry-contact limits (max 30VDC/6A or 70VDC/1A or 125VAC/6A) and proper configuration for two-wire generator integration.

Interactive Parameters & Live Verdict

Rule Diagnostics & Recommendations

    Engineering Formula & Verification Notes

    Calculations evaluate the Cerbo GX Relay 1 trigger condition based on battery State of Charge (SOC) comparison logic. The Cerbo GX utilizes potential-free Normally Open (NO) and Normally Closed (NC) dry contacts on Relay 1 to bridge a two-wire generator start signal.

    Configuring Victron Cerbo GX Relay 1 for Generator Auto Start

    To configure auto-start on a Victron Cerbo GX, wire your generator's two-wire start leads to the COMMON and NORMALLY OPEN ports on Relay 1. Then navigate in VRM or the GX Touch to Settings -> Relay -> Function Relay 1 and set it to 'Generator start/stop'. Next, enable 'Automatic start' under Settings -> Generator start/stop -> Conditions.

    • Always verify your generator is a two-wire start type (or equipped with a 3-wire to 2-wire adapter).
    • Set Relay 1 strictly for generator start/stop functionality as Relay 2 lacks generator firmware integration.
    • Configure time delays to ignore momentary voltage sags or spikes.

    Tank Level Sensor & Fuel Calibration Best Practices

    When integrating tank level sensors for generator fuel monitoring or tank pump automation, match your resistance inputs (e.g., 0-180 ohm or 240-33 ohm standards) in the GX menu. Calibrate empty and full calibration points accurately to prevent false triggers.

    • Check sender resistance compatibility before wiring to analog inputs.
    • Ensure proper ground referencing between the tank sender and the Cerbo GX.

    Cerbo GX Relay Electrical Rating Benchmarks

    Cerbo GX Relay Electrical Rating Benchmarks
    Circuit Type Max Voltage Limit Max Current Limit
    Low Voltage DC Up to 30 VDC 6 A
    Medium Voltage DC Up to 70 VDC 1 A
    Alternating Current (AC) 125 VAC 6 A

    Frequently Asked Technical Questions

    Which Cerbo GX relay must be used for generator auto start?

    Relay 1 must be used. Relay 1 supports generator start/stop, alarm relay, and tank pump functions, whereas Relay 2 is restricted to temperature control and manual operation.

    How should a 2-wire generator be wired to the Cerbo GX?

    Connect the two wires from your generator to the COMMON and NORMALLY OPEN (NO) terminals on Relay 1 of the Cerbo GX.

    What is the recommended minimum battery SOC for auto-start?

    It is recommended not to go lower than 20% to 30% SOC to prevent risking battery damage, low voltage disconnects, and unintended shutdowns of the GX device.